DIESEL 10 LC A SILENCE UK C5

Generating set

DIESEL 10 LC A SILENCE UK C5 Portable Power Generating set, equipped with KOHLER engine.

Documentation Print

Direct access to sections

GENERAL SPECIFICATIONS

Range DIESEL
Frequency (Hz) 50 Hz
Max power (kW) 8.30
Nominal voltage (V) 230
Number of Phase Single phase
Fuel Diesel Fuel
Tank (L) 27
75% cons. (l/h) 2.60
75% Autonomy (h) 10.40

ENGINE SPECIFICATIONS

Engine brand KOHLER
Engine ref. KDW702
Distribution Diesel O.H.V.
Start Electrical
Oil shutdown OUI
Displacement (cm3) 686
Oil system capacity including filters (l) 1.60

ALTERNATOR SPECIFICATIONS

Technology Brushless
AVR Regulation No
Indication of protection IP 23
Insulation class H

PLUGS AND PANEL DESCRIPTIVE

Plug type UK 2 115V 16A sockets - circuit breaker + 2 115V 32A sockets - circuit breaker + 1 230V 16A socket - circuit breaker + 1 230V 32A socket - circuit breaker + emergency stop button + hour meter + indicator + APM202

PRODUCT ADVANTAGES

Entire group guaranteed 3 years
KOHLER water-cooled industrial engine
Very Silent
Soundproofing and against shocks panels
Hydrocarbons bulk tank

ACCESSORIES SUPPLIED

User and maintenance manual
Lifting eye
Battery without maintenance
Hour meter

OPTIONS

Réf. 2 Description
RSTART2 Remote control in order to start or stop the generating set until a distance of 50 meters (needs the APM202 control panel)
VERSO50 Switches over automatically if the mains fails, 40A or 100A 1P or if the mains fails, 25A or 40A 3P (needs the installation of a APM202 control panel). Includes the battery charger.
R05M The manual changeover switch is used to connect and disconnect a generating set manually to a domestic circuit when there is a power cut.
RPQ For earthing your generator set. Galvanised 1 m long spike, supplied with 2 m of 10 mm² cable.